Three layouts, the same core data
The STS offers three home screen styles: Mimic, Multigauge and Analog/Digital. Each shows line pressure, the current mode and a Status panel of machine statistics. Status values are read-only, so nothing on the home screen changes a setting (§2.1, p. 7).
State: what the compressor is doing
The State field shows how the compressor is responding to its mode and current conditions. Sullair lists 21 states (§2.1, p. 7). The manual names them without defining each one, so the grouping below is ours, based on the state names.
| Group | States as shown on the STS |
|---|---|
| Starting | INITIALIZING, STARTING 1, STARTING 2, STARTING 3, PRECOOLING THE DRYER, RESTARTING |
| Running loaded | LOADING, LOADED & MODULATING, FULLY LOADED |
| Unloading or unloaded | UNLOADING, REMOTE UNLOADING, RUNNING UNLOADED, REMOTE UNLOADED |
| Stopping or stopped | STOPPING, MANUALLY STOPPED, REMOTE STOPPING, REMOTE STOPPED |
| Waiting | STANDING BY, WAITING FOR BLOWDOWN |
| Fault | FAULTING, FAULTED |
Standing by is not switched off. If the green indicator blinks slowly, the motor is stopped in Automatic mode and may restart at any time (§1.2, p. 6).
Mode: how operation is controlled
Mode shows the way the machine’s operation is being controlled. There are five modes: AUTOMATIC, MANUAL, OFF, FAULT and UI COMM (§2.1, p. 7).
When a Fault or Warning icon appears, Sullair says the Mode field tells you the reason (§2.1.1, p. 8). Write it down with the message.
Status readings
| Field | What it shows |
|---|---|
| Starts | Times the compressor has been started, automatically or manually |
| Cycles | Load cycles completed |
| Run | Hours the compressor motor has run |
| Load | Hours the compressor has run loaded |
| Discharge Temperature | Internal temperature of the compressor |
| Sump Pressure | Compressor sump pressure (P1) |
| Line Pressure | Pressure leaving the package (P2) |
Source: §2.1 (p. 7); P1 and P2 labels from §2.1 (p. 8) and §3.2.2 (p. 12). The manual calls line pressure the compressor’s discharge pressure on the home screen and the package outlet pressure on Machine Information.
For more counters, such as full-load hours, oil filter pressure and oil pressure, open Machine Information (§3.2.2, p. 12):
Menu, then System Information, then Machine Information
dP1 and the capacity bar
The Mimic screen shows dP1: sump pressure (P1) minus line pressure (P2). It is the separator pressure differential behind the High Separator dP warning (§2.1, pp. 7–8).
The Mimic and Multigauge screens also have a Capacity bar, showing the air being delivered as a percentage of full capacity. It is an instantaneous figure, based on spiral valve position or on the percentage of maximum VSD frequency (§2.1, p. 8).
Fault and Warning icons
An icon button appears whenever there is a fault or a warning, and its design shows which one it is (§2.1.1, p. 8):
- Fault icon: opens Event History, where you can see when the fault happened (pp. 8–9).
- Warning icon: opens the Recommended Service screen for a service reminder, or the Warnings screen for a machine warning (pp. 8–9).
Touch lightly
Operate the touch screen with a finger or stylus and moderate force only, never a tool (§2.1, p. 7). Excessive force can damage the screen; one symptom Sullair lists is the touchscreen going into calibration mode (Table 6-1, p. 30).
Source
Based on Sullair STS Controller User Manual, part 02250241-178 R01, referenced pages 6, 7, 8, 9, 12, 30. Sections used: §1.2 (p. 6), §2.1 (pp. 7–8), §2.1.1 (pp. 8–9), §3.2.2 (p. 12), Table 6-1 (p. 30). Written in our own words; check the manual for the exact wording.