OEM-based guide

How to reset Sullair STS warnings and faults safely

What the Start and Stop buttons clear on a Sullair STS controller, why a fault returns after a power cut, and what to check before any reset.

Safety first: a stopped compressor can start

Read this before you touch the panel. A quiet machine is not a safe machine. Watch the indicators (§1.2, p. 6):

  • Green, slow blink: the motor is stopped in Automatic mode and may restart at any time. A rapid blink means a start is imminent.
  • Blue, slow blink: Automatic Restart After Power Failure is enabled.

The Start button’s main job is to start the compressor (§1.2, p. 6). Pressing it on a stopped machine can start the machine, so treat it as a start command, never as a harmless “clear” button.

Never work on the package because it looks stopped. Sullair’s own service steps begin by stopping the compressor and locking out power (§6.4, p. 35). Electrical, pressurized and rotating parts need isolation under lockout/tagout.

Before you press Start or Stop

  1. Read the display and the indicator. Note the exact message and whether the amber or red indicator is lit, then look the message up in the Sullair STS list.
  2. Record the evidence. Event History keeps the 16 most recent warning, fault and alarm messages (§3.4.3, p. 21). For a longer record, save the Event Log report to USB (STS reports).
  3. Look before you repair. Sullair recommends a detailed visual inspection before attempting any repair (§6.1, p. 29). Start with the safe first checks.
  4. Fix the cause, then clear the message. If the same message comes back after a reset, stop resetting and hand the record to a qualified technician.

What the Start and Stop buttons clear

Sullair documents a second function for each panel button (§1.2, p. 6):

  • Start can also reset maintenance and warning messages. That function is documented for a compressor that is already running. On a stopped compressor, Start is a start command.
  • Stop can also clear fault messages once the compressor is stopped.

Clearing a message does not repair the underlying fault. A red fault keeps the compressor inoperative until the fault condition itself is corrected (§1.2, p. 6), so a reset only helps after the cause has been dealt with.

What clears what

What clears each STS message type
Message typeIndicatorCompressorHow it is cleared
WarningAmberIn most cases keeps running (§1.2, p. 6)Start button, while the compressor is running (§1.2, p. 6)
Service reminderAmberIn most cases keeps running (§1.2, p. 6)After the maintenance is done, reset the reminder on the Recommended Service screen (Table 6-1, p. 30)
FaultRed, steadyStays inoperative until the fault condition is corrected (§1.2, p. 6)Correct the cause, then press Stop with the compressor stopped (§1.2, p. 6; §6.3, p. 35)

Not sure which you have? See Warning vs Fault and service reminders.

Why a fault is still there after a power cut

Sullair describes three outcomes when power returns (§6.3, p. 35):

  • Faulted before the outage: the controller returns to the faulted condition and shows the reason. Repair the cause, then press Stop to reset.
  • Manually stopped before the outage: it returns to the manually stopped state and needs a manual restart with Start. Restart only by following the machine-specific, authorized startup procedure, once the package is confirmed clear and safe to start.
  • In Automatic or Manual mode with a restart timer above zero: it resumes that mode once the timer runs out. No key press is needed, so the compressor can start by itself.

Power Interruption is itself on the STS warning list (§3.4.1, p. 20).

The E-stop is not a reset button

Sullair says the E-stop stops the compressor immediately, that a press is logged as a fault, and that it should only be used when essential (§1.2, p. 6). Keep it for emergencies. Afterwards, expect an E-Stop Push Button message; the troubleshooting table’s first remedy is to release the button (Table 6-1, p. 31).

Source

Based on Sullair STS Controller User Manual, part 02250241-178 R01, referenced pages 5, 6, 20, 21, 29, 30, 31, 35. Sections used: §1.2 (pp. 5–6), §3.4.1 (p. 20), §3.4.2.1 (p. 20), §3.4.3 (p. 21), §6.1 (p. 29), Table 6-1 (pp. 30–31), §6.3 and §6.4 (p. 35). Written in our own words; check the manual for the exact wording.

Open the Sullair manual

Safety: Use this as a reference, not a substitute for the machine-specific operator manual, site procedures, lockout/tagout and qualified service.