OEM tracedhigh severityFault

Low Sump Pressure

The controller is not seeing the expected sump pressure for the machine state.

What it means

The controller is not seeing the expected sump pressure for the machine state.

The STS troubleshooting table links this message to either a pressure-sensing problem or a compressor that did not actually start correctly.

Likely causes

  • Pressure sensor, connection, wiring or tubing problem
  • Machine failed to start or did not reach the expected operating state

Operator-safe first checks

  • Confirm whether the main motor actually started and note any other simultaneous faults.
  • Record the sump-pressure value shown on the controller.
  • Do not loosen pressure tubing or fittings on a pressurized package.

Trained maintenance / service checks

  • Check the pressure sensor, wiring, connections and sensing tubing.
  • Diagnose the start sequence if the machine failed to start.

Can the compressor keep running?

No. Diagnose the failed start or pressure-sensing condition before returning the compressor to service.

Source confidence

OEM VERIFIED

Sullair identifies bad sensor/connections or a failed start as causes of Low Sump Pressure.

Source: Sullair STS Controller User Manual, part 02250241-178 R01. Referenced manual page(s): 33.

Open the Sullair manual

Safety: Industrial compressors can contain hazardous electrical energy, automatic-restart functions, rotating machinery, hot fluid and stored pneumatic pressure. Do not open electrical cabinets, pressure vessels or pressurized connections unless you are trained, authorized and following lockout/tagout and depressurization procedures.